Title: Operating characteristics and efficiencies of an active chilled beam terminal unit under variable air volume mode
Authors: Chen, Can
Cai, Wenjian
Wang, Youyi
Lin, Chen
Wang, Lei
Keywords: DRNTU::Engineering::Electrical and electronic engineering::Power electronics
Issue Date: 2015
Source: Chen, C., Cai, W., Wang, Y., Lin, C., & Wang, L. (2015). Operating characteristics and efficiencies of an active chilled beam terminal unit under variable air volume mode. Applied Thermal Engineering, 85, 71-79.
Series/Report no.: Applied thermal engineering
Abstract: Appropriately designing and maintaining temperature and relative humidity in a given space is essential for active chilled beam systems, where condensation should be strictly prevented. As a consequence, the Total Cooling Output Capacity (TCOC) of an active chilled beam system should be matched with the total cooling load of the applied space, as well as the Sensible Heat Ratio (SHR) of the system with the SHR of the space. From such a perspective, this paper for the first time explored the operating characteristics of a 2-way discharge active chilled beam terminal unit. Based on an experimentally verified model of the unit, a series of realistic simulations were carried out under various primary air volume flow rates and various chilled water volume flow rates. Inherent correlations between the TCOC and SHR were revealed. In the meanwhile, the operating efficiencies of the unit were also measured by an energy saving potential index ɛ, which is defined as the ratio of chilled water sensible cooling output capacity to the total sensible cooling output capacity. In addition, influences of different primary air and space conditions on the operating characteristics and efficiencies were studied. The results obtained in this study are expected to facilitate a better understanding of the active chilled beam terminal unit, so as to the designs, the operating principles, and the control strategies of active chilled beam systems for an improved indoor thermal environment.
URI: https://hdl.handle.net/10356/96290
http://hdl.handle.net/10220/38484
ISSN: 1359-4311
DOI: 10.1016/j.applthermaleng.2015.03.016
Schools: School of Electrical and Electronic Engineering 
Rights: © 2015 Elsevier Ltd. This is the author created version of a work that has been peer reviewed and accepted for publication by Applied Thermal Engineering, Elsevier Ltd. It incorporates referee’s comments but changes resulting from the publishing process, such as copyediting, structural formatting, may not be reflected in this document. The published version is available at: [http://dx.doi.org/10.1016/j.applthermaleng.2015.03.016].
Fulltext Permission: open
Fulltext Availability: With Fulltext
Appears in Collections:EEE Journal Articles

SCOPUSTM   
Citations 20

10
Updated on Mar 20, 2024

Web of ScienceTM
Citations 20

9
Updated on Oct 30, 2023

Page view(s) 50

470
Updated on Mar 27, 2024

Download(s) 20

193
Updated on Mar 27, 2024

Google ScholarTM

Check

Altmetric


Plumx

Items in DR-NTU are protected by copyright, with all rights reserved, unless otherwise indicated.