dc.identifier.citationLi, C., Yan, J., Li, Y., Cai, W., Lin, C., & Chen, H. (2016). Experimental study on a multi-evaporator refrigeration system with variable area ratio ejector. Applied Thermal Engineering, 102, 196-203.en_US
dc.identifier.issn1359-4311en_US
dc.identifier.urihttp://hdl.handle.net/10220/42089
dc.description.abstractThis paper describes an experimental study on a multi-evaporator refrigeration system (MERS) with conventional pressure regulating valve (PRV) and variable area ratio ejector. Some key performance indicators such as cooling capacity, power consumption and ejector entrainment ratio were evaluated by switching operating modes, adjusting superheat and tuning ejector spindle and so on. The results indicated that: (1) the energy efficiency of the MERS can be improved by up to 12% by replacing the conventional pressure regulating valve with the variable area ratio ejector, (2) sufficient superheat or superheat degree greater than 2 °C is conducive to high entrainment performance of the ejector, large cooling capacity of the low-temperature evaporator and low power consumption of the system, and (3) the effect of nozzle spindle position on the performance of the system is evident.en_US
dc.description.sponsorshipASTAR (Agency for Sci., Tech. and Research, S’pore)en_US
dc.format.extent28 P.en_US
dc.language.isoenen_US
dc.relation.ispartofseriesApplied Thermal Engineeringen_US
dc.rights© 2016 Elsevier Ltd. This is the author created version of a work that has been peer reviewed and accepted for publication by Applied Thermal Engineering, Elsevier Ltd. It incorporates referee’s comments but changes resulting from the publishing process, such as copyediting, structural formatting, may not be reflected in this document. The published version is available at: [http://dx.doi.org/10.1016/j.applthermaleng.2016.04.006].en_US
dc.subjectMulti-evaporator refrigeration systemen_US
dc.subjectVariable area ratio ejectoren_US
dc.titleExperimental study on a multi-evaporator refrigeration system with variable area ratio ejectoren_US
dc.typeJournal Article
dc.contributor.schoolSchool of Electrical and Electronic Engineeringen_US
dc.identifier.doihttp://dx.doi.org/10.1016/j.applthermaleng.2016.04.006
dc.description.versionAccepted versionen_US


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record