dc.identifier.citationChaudhuri, T., Soh, Y. C., Bose, S., Xie, L., & Li, H. (2016). On assuming Mean Radiant Temperature equal to air temperature during PMV-based thermal comfort study in air-conditioned buildings. IECON 2016 - 42nd Annual Conference of the IEEE Industrial Electronics Society, 7065-7070.en_US
dc.identifier.urihttp://hdl.handle.net/10220/42211
dc.description.abstractMean Radiant Temperature (MRT) is an important factor of Fanger's PMV model, which is the most popular method to study human thermal comfort. However, it has often been a practice to assume MRT equal to air temperature (Ta) during indoor thermal studies. In this paper, we have studied the consequences of this simplistic assumption on the thermal comfort of occupants in air-conditioned buildings. A worldwide database of about 10000 occupants covering 9 climatic zones and 4 seasons has been studied. The effect on comfort indices-Predicted Mean Vote (PMV), Actual Mean Vote (AMV), Thermal Acceptability Vote (TSA) and Thermal Preference Vote (MCI) are presented. It is observed that even a small difference in Ta and MRT can lead to significant error in determination of thermal comfort. A correlation study between AMV and the six Macpherson factors reveals that MRT has the highest positive correlation with the thermal sensation reported by the occupants. Study of TSA and MCI show that the assumption is more likely to affect comfort level determination in the uncomfortable range.en_US
dc.description.sponsorshipNRF (Natl Research Foundation, S’pore)en_US
dc.format.extent6 p.en_US
dc.language.isoenen_US
dc.rights© 2016 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works. The published version is available at: [http://dx.doi.org/10.1109/IECON.2016.7793073].en_US
dc.subjectmean radiant temperatureen_US
dc.subjectcomfort level determinationen_US
dc.titleOn assuming Mean Radiant Temperature equal to air temperature during PMV-based thermal comfort study in air-conditioned buildingsen_US
dc.typeConference Paper
dc.contributor.conferenceIECON 2016 - 42nd Annual Conference of the IEEE Industrial Electronics Societyen_US
dc.contributor.researchEnergy Research Institute @NTU
dc.contributor.schoolSchool of Electrical and Electronic Engineeringen_US
dc.contributor.schoolSchool of Mechanical and Aerospace Engineeringen_US
dc.identifier.doihttp://dx.doi.org/10.1109/IECON.2016.7793073