Please use this identifier to cite or link to this item: https://hdl.handle.net/10356/160300
Title: Model predictive control for integrated control of air-conditioning and mechanical ventilation, lighting and shading systems
Authors: Yang, Shiyu
Wan, Man Pun
Ng, Bing Feng
Dubey, Swapnil
Henze, Gregor P.
Chen, Wanyu
Baskaran, Krishnamoorthy
Keywords: Engineering::Mechanical engineering
Issue Date: 2021
Source: Yang, S., Wan, M. P., Ng, B. F., Dubey, S., Henze, G. P., Chen, W. & Baskaran, K. (2021). Model predictive control for integrated control of air-conditioning and mechanical ventilation, lighting and shading systems. Applied Energy, 297, 117112-. https://dx.doi.org/10.1016/j.apenergy.2021.117112
Project: NRF2015ENC-GBICRD001-020 
GBIC-R&D/DCP02 
Journal: Applied Energy 
Abstract: Modern buildings are increasingly automated and often equipped with multiple building services (e.g., air-conditioning and mechanical ventilation (ACMV), dynamic shading, dimmable lighting). These systems are conventionally controlled individually without considering their interactions, affecting the building's overall energy inefficiency and occupant comfort. A model predictive control (MPC) system that features a multi-objective MPC scheme to enable coordinated control of multiple building services for overall optimized energy efficiency, indoor thermal and visual comfort, as well as a hybrid model for predicting indoor visual comfort and lighting power is proposed. The MPC system was implemented in a test facility having two identical, side-by-side experimental cells to facilitate comparison with a building management system (BMS) employing conventional reactive feedback control. The MPC system coordinated the control of the ACMV, dynamic façade and automated dimmable lighting systems in one cell while the BMS controlled the building services in the other cell in a conventional manner. The MPC side achieved 15.1–20.7% electricity consumption reduction, as compared to the BMS side. Simultaneously, the MPC system improved indoor thermal comfort by maintaining the room within the comfortable range (−0.5 < predicted mean vote < 0.5) for 98.3% of the time, up from 91.8% of the time on the BMS side. Visual comfort, measured by indoor daylight glare probability (DGP) and horizontal illuminance level at work plane height, was maintained for the entire test period on the MPC side, improving from having visual comfort for 94.5% and 85.7% of the time, respectively, on the BMS side.
URI: https://hdl.handle.net/10356/160300
ISSN: 0306-2619
DOI: 10.1016/j.apenergy.2021.117112
Schools: School of Mechanical and Aerospace Engineering 
Research Centres: Energy Research Institute @ NTU (ERI@N) 
Rights: © 2021 Elsevier Ltd. All rights reserved.
Fulltext Permission: none
Fulltext Availability: No Fulltext
Appears in Collections:ERI@N Journal Articles
MAE Journal Articles

SCOPUSTM   
Citations 10

32
Updated on Oct 1, 2023

Web of ScienceTM
Citations 10

29
Updated on Sep 28, 2023

Page view(s)

69
Updated on Oct 3, 2023

Google ScholarTM

Check

Altmetric


Plumx

Items in DR-NTU are protected by copyright, with all rights reserved, unless otherwise indicated.