Title: Experimental indirect cooling performance analysis of the metal 3D-printed cold plates with two different supporting elements
Authors: Kanbur, Baris Burak
Seat, Mun Hoe
Markussen, Wiebke Brix
Kærn, Martin Ryhl
Duan, Fei
Keywords: Engineering::Mechanical engineering
Issue Date: 2023
Source: Kanbur, B. B., Seat, M. H., Markussen, W. B., Kærn, M. R. & Duan, F. (2023). Experimental indirect cooling performance analysis of the metal 3D-printed cold plates with two different supporting elements. International Communications in Heat and Mass Transfer, 148, 107046-. https://dx.doi.org/10.1016/j.icheatmasstransfer.2023.107046
Project: RG154/19 
Journal: International Communications in Heat and Mass Transfer 
Abstract: This study experimentally investigates the cooling time and performance of two new cold plate designs manufactured via selective laser melting process using body-centred cubic (BCC) and pillar elements. The plates are cooled down from the initial surface temperature of 45 °C to the target surface temperature of 32.5 °C under tropical conditions at three different volume flow rates and two different inlet water temperatures. The minimum cooling time is found at 30 s and 63 s at the highest volume flow rate and the lowest inlet water temperature for the pillar- and BCC-filled plates, respectively. The greatest plate and system COP values are 1195.1 and 6.8 for the BCC-filled plate and 1192.0 and 6.2 for the pillar-filled plate, respectively, at the minimum flow rate and the inlet water temperature. The performance evaluation criterion range is 1.25 to 1.28 and 2.12 to 2.52 for the BCC- and pillar-filled plates, respectively. The heat transfer coefficient dramatically increases by rising the volume flow rate at the low inlet water temperature case but the increasing trends become slighter at the high inlet water temperature case. Tropical climate results in high dew point temperatures, therefore, cooling with high inlet water temperature is found ineffective.
URI: https://hdl.handle.net/10356/173196
ISSN: 0735-1933
DOI: 10.1016/j.icheatmasstransfer.2023.107046
Schools: School of Mechanical and Aerospace Engineering 
Rights: © 2023 The Author(s). Published by Elsevier Ltd. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
Fulltext Permission: open
Fulltext Availability: With Fulltext
Appears in Collections:MAE Journal Articles

Files in This Item:
File Description SizeFormat 
1-s2.0-S0735193323004359-main.pdf5.78 MBAdobe PDFThumbnail
View/Open

SCOPUSTM   
Citations 50

3
Updated on May 5, 2025

Page view(s)

86
Updated on May 6, 2025

Download(s) 50

22
Updated on May 6, 2025

Google ScholarTM

Check

Altmetric


Plumx

Items in DR-NTU are protected by copyright, with all rights reserved, unless otherwise indicated.