Please use this identifier to cite or link to this item: https://hdl.handle.net/10356/89303
Title: Dynamic modeling and validation of a liquid desiccant cooling and dehumidification system
Authors: Ou, Xianhua
Cai, Wenjian
He, Xiongxiong
Zhai, Deqing
Wang, Xinli
Keywords: Cooling Coil
Dehumidifier
Issue Date: 2017
Source: Ou, X., Cai, W., He, X., Zhai, D., & Wang, X. (2018). Dynamic modeling and validation of a liquid desiccant cooling and dehumidification system. Energy and Buildings, 163, 44-57.
Series/Report no.: Energy and Buildings
Abstract: In this study, a simplified dynamic model for the liquid desiccant cooling and dehumidification system (LDCDS) is developed from a control viewpoint based on the laws of conservation of energy and mass. The complete LDCDS consists of three subsystems, namely the cooling coil, dehumidifier and cooler in which the models can be estimated separately and combined to obtain the model of LDCDS. The heat and mass transfer rates in model are derived through effectiveness-NTU and hybrid modeling approaches. The parameters of the thermal and moisture dynamic models are pre-identified by using the Levenberg–Marquardt method with static experimental data from the LDCDS pilot plant and then refined by adopting an unscented Kalman filter algorithm with dynamic experimental data. Detailed experimental tests on a pilot plant reveal that the proposed model accurately predicts the system performance under different operating conditions. The proposed model is expected to be applied in further research on the effects of more advanced control and optimization algorithms with the system energy efficiency.
URI: https://hdl.handle.net/10356/89303
http://hdl.handle.net/10220/44879
ISSN: 0378-7788
DOI: 10.1016/j.enbuild.2017.12.041
Schools: School of Electrical and Electronic Engineering 
Research Centres: Centre for System Intelligence and Efficiency (EXQUISITUS) 
Rights: © 2017 Elsevier B.V. This is the author created version of a work that has been peer reviewed and accepted for publication by Energy and Buildings, Elsevier B.V. It incorporates referee’s comments but changes resulting from the publishing process, such as copyediting, structural formatting, may not be reflected in this document. The published version is available at: [http://dx.doi.org/10.1016/j.enbuild.2017.12.041].
Fulltext Permission: open
Fulltext Availability: With Fulltext
Appears in Collections:EEE Journal Articles

Files in This Item:
File Description SizeFormat 
Dynamic modeling and validation of a liquid desiccant.pdf5.02 MBAdobe PDFThumbnail
View/Open

SCOPUSTM   
Citations 20

17
Updated on May 3, 2025

Web of ScienceTM
Citations 20

13
Updated on Oct 27, 2023

Page view(s) 10

1,020
Updated on May 5, 2025

Download(s) 20

372
Updated on May 5, 2025

Google ScholarTM

Check

Altmetric


Plumx

Items in DR-NTU are protected by copyright, with all rights reserved, unless otherwise indicated.