Title: Short-time fourier transform based transient analysis of VSC interfaced point-to-point DC system
Authors: Satpathi, Kuntal
Yeap, Yew Ming
Ukil, Abhisek
Geddada, Nagesh
Keywords: Fault Analysis
DRNTU::Engineering::Electrical and electronic engineering
DC Grid
Issue Date: 2018
Source: Satpathi, K., Yeap, Y. M., Ukil, A., & Geddada, N. (2018). Short-time fourier transform based transient analysis of VSC interfaced point-to-point DC system. IEEE Transactions on Industrial Electronics, 65(5), 4080-4091. doi:10.1109/TIE.2017.2758745
Series/Report no.: IEEE Transactions on Industrial Electronics
Abstract: The transient response of the voltage source converter (VSC) interfaced dc system is significantly different from the ac counterpart. The rapid discharge current from the dc-link capacitors and the vulnerability of the freewheeling diodes during the short circuit in dc grid demand that the transient detection algorithm executes within a few milliseconds. The rapidly rising fault current in the dc grid is expected to have high-frequency components which might be an effective indicator of the transient condition. This paper presents quantitative investigation of the high-frequency components utilizing short-time Fourier transform (STFT) during transient conditions. Detailed operating principles with various factors affecting the STFT operation such as ripple content of the input dc signal and window type and length have been thoroughly investigated. STFT algorithm is able to detect low-impedance faults within 1 ms and high-impedance faults in 2 ms. Moreover, it is able to distinguish between short-circuit fault and less severe transient conditions such as sudden load change. The STFT algorithm is evaluated analytically and subsequently applied to a MATLAB/Simulink based dc test system. It is further validated and substantiated with the real fault current data obtained from a scaled-down experimental testbed. Sensitivity analysis and comparison with the existing frequency-domain-based fault-detection method are done to support the efficacy of the proposed method.
URI: https://hdl.handle.net/10356/90241
http://hdl.handle.net/10220/48775
ISSN: 0278-0046
DOI: 10.1109/TIE.2017.2758745
Schools: School of Electrical and Electronic Engineering 
Rights: © 2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works. The published version is available at: https://doi.org/10.1109/TIE.2017.2758745.
Fulltext Permission: open
Fulltext Availability: With Fulltext
Appears in Collections:EEE Journal Articles

Files in This Item:
File Description SizeFormat 
ALL_17-TIE-1276-ls.pdfAccepted_Version2.03 MBAdobe PDFThumbnail
View/Open

SCOPUSTM   
Citations 5

180
Updated on Apr 20, 2025

Web of ScienceTM
Citations 5

117
Updated on Oct 26, 2023

Page view(s) 50

517
Updated on May 7, 2025

Download(s) 10

420
Updated on May 7, 2025

Google ScholarTM

Check

Altmetric


Plumx

Items in DR-NTU are protected by copyright, with all rights reserved, unless otherwise indicated.